top of page

HIGH YIELD

Advanced three-level technology, max. inverter

efficiency 99 %

Effective cooling, full power operation at 45 ℃

SMART O&M

Integrated zone monitoring function for online analysis and

trouble shooting

Modular design, easy for maintenance

SAVED INVESTMENT

Low transportation and installation cost due to

outdoor design

DC 1500 V system, low system cost

Q at night function optional

 

ype designation

SG3300UD

SG4400UD

Input (DC)

Max. PV input voltage

1500 V

Min. PV input voltage / Startup input voltage

895 V / 905 V

MPP voltage range

895 V – 1500 V

No. of independent MPP inputs

3

4

No. of DC inputs

15 ( optional: 21 )

20 ( optional: 28 )

Max. PV input current

3 * 1435 A

4 * 1435 A

Max. DC short-circuit current

3 * 3528 A

4 * 3528 A

PV array configuration

Negative grounding or floating

Output (AC)

AC output power

3300 kVA @ 45 ℃

3399 kVA @ 40 ℃

3795 kVA @ 22.5 ℃

4400 kVA @ 45 ℃

4532 kVA @ 40 ℃

5060 kVA @ 22.5 ℃

Max. AC output current

3 * 1160 A

4 * 1160 A

Nominal AC voltage

630 V

AC voltage range

536 V – 693 V

Nominal grid frequency / Grid frequency range

50 Hz / 45 Hz – 55 Hz, 60 Hz / 55 Hz – 65 Hz

Harmonic (THD)

< 1.5 % ( at nominal power )

Power factor at nominal power / Adjustable power factor

> 0.99 / 0.8 leading – 0.8 lagging

Feed-in phases / AC connection

3 / 3

Efficiency

Max. efficiency / European efficiency

99.0 % / 98.8 %

Protection & Function

DC input protection

Load break switch + fuse

AC output protection

Circuit breaker

Overvoltage protection

DC Type II / AC Type II

Grid monitoring / Ground fault monitoring

Yes / Yes

Insulation monitoring

Yes

Surge protection

Yes

Q at night function

Optional

General data

Dimensions (W*H*D)

2340 mm * 2300 mm * 1550 mm

2900 mm * 2300 mm * 1550 mm

Weight

2.5 T

3.3 T

Topology

Transformerless

Degree of protection

IP65

Night power consumption

< 200 W

Operating ambient temperature range *

-35 ℃ - 60 ℃ ( > 45 ℃ derating )

Allowable relative humidity range

0 % – 100 %

Cooling method

Temperature controlled forced air cooling

Max. operating altitude

4000 m ( > 3000 m derating )

Display

LED indicators, Ethernet + WebHMI

Communication

Standard: RS485, Ethernet

Compliance

CE, IEC 62109, IEC 61727, IEC 62116, IEC 60068, IEC 61683, VDE-AR-N

4110:2018, VDE-AR-N 4120:2018, EN 50549-2, UNE 206007-1:2013, NTS 631,

UTE C15-712-1:2013

---------------------------------------------------------------------------

Type designation

SG3300UD-MV-20

Input (DC)

Max. PV input voltage

1500 V

Min. PV input voltage / Startup input voltage

938 V / 950 V

MPP voltage range

938 V – 1500 V

No. of independent MPP inputs

3

No. of DC inputs

15 ( optional: 21 )

Max. PV input current

3 * 1435 A

Max. DC short-circuit current

3 * 3528 A

PV array configuration

Negative grounding or floating

Output (AC)

AC output power

3300 kVA @ 51 ℃, 3960 kVA @ 23 ℃

Max. inverter output current

3 * 1155 A

Max. AC output current

229 A

Rated voltage range

10 kV – 35 kV

Nominal grid frequency / Grid frequency range

50 Hz / 45 Hz – 55 Hz, 60 Hz / 55 Hz – 65 Hz

Harmonic (THD)

< 1.5 % ( at nominal power )

Power factor at nominal power / Adjustable power factor

>0.99 / 0.8 leading – 0.8 lagging

Feed-in phases / AC connection

3 / 3

Efficiency

Inverter max. efficiency / Inverter European efficiency

99.0 % / 98.7 %

Transformer

Transformer rated power

3300 kVA

Transformer max. power

3960 kVA

LV / MV voltage

0.66 kV / 0.66 kV / (10 – 35) kV

Impedance

7%(0 % - ± 10 %)@ 3300 kVA

Transformer vector

Dy11

TTransformer cooling method

ONAN ( Oil-natural, air-natural )

Oil type

Mineral oil ( PCB free )

Protection & Function

DC input protection

DC load switch + fuse

Inverter output protection

AC circuit breaker

AC MV output protection

AC circuit breaker

Surge protection

DC Type II / AC Type II

Grid monitoring / Ground fault monitoring

Yes / Yes

Insulation monitoring

Yes

Overheat protection

Yes

Q at night function

Optional

General data

Dimensions (W*H*D)

6058 mm * 2896 mm * 2438 mm

Weight

17.5 T

Degree of protection

Inverter: IP65 / Others: IP54

Auxiliary power supply

15 kVA ( optional: max. 30 kVA )

Operating ambient temperature range *

-35 ℃ – 60 ℃ ( > 51 ℃ derating )

Allowable relative humidity range

0 % – 100 %

Cooling method

Temperature controlled forced air cooling

Max. operating altitude

1000 m ( standard ) / > 1000 m ( optional )

Display

LED Indicators, WLAN + WebHMI

Communication

Standard: RS485, Ethernet

Compliance

CE, IEC 62109, IEC 61727, IEC 62116, IEC 60068, IEC 61683, IEC62271-202

SG3300/4400UD

CA$0.00Prix
Quantité
bottom of page